NIBS

Testing for Telecom End User Testing for Telecom End User

NiBS have recently been doing some testing for a major telecom end user.  For all testing NiBS datalog cell or block voltage throughout the test, and the current and temperature to ensure consistency.  In the case of all witness tests besides a very accurate clamp meter, we use a shunt to confirm the current being measured. The attached photo shows that in this case the test was also being done to check the fit of these particular batteries in a new design of cubicle.  The batteries passed a 3 hour test very well and all parties were satisfied with the outcome.